West Sterlington Water System
On record since 2004: 34 violations. 28 over the limit · 1 treatment lapse · 1 missed or late test · 4 notices or reports. Most recent began 2025-07-01.
For this year's test results, ask the utility for its annual Consumer Confidence Report. Every community system must publish one.
More violations on record than 87% of active water systems in Louisiana. Small systems with no staff chemist often rack up missed-test violations; big utilities rarely do.
The record, year by year
Across Louisiana, 31% of violations are missed or late tests and 25% are water over a limit.
How far over the limit
Lead & copper at the tap
Utilities sample taps in homes most likely to have lead pipes, and report the 90th-percentile result: 9 in 10 homes sampled came in at or below this number. Above the red line (the action level) the utility must act. The action level is not a safe level; EPA's health goal for lead is zero. EPA's file does not date these results, so they are shown highest first.
Lead, 90th percentile 4 results on file · action level 15 ppb
Every violation on record
- 2025-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2670 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2025-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2640 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2025-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2720 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2024-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2700 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2024-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2790 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2024-06-15Public NoticePN Violation for NPDWR ViolationBack in compliance
- 2024-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2870 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2024-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2580 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2023-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2560 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2023-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2460 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2023-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2160 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2023-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2260 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2022-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2220 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2022-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2170 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2022-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2270 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2022-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2520 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2021-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2550 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2021-10-01Groundwater RuleFailure To Address DeficiencyBack in compliance
- 2021-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2600 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2021-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2550 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2021-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2390 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2020-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2390 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2020-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2390 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2020-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2400 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2020-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2220 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
Show the other 9 entries
- 2019-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2010 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2019-09-10Public NoticePN Violation for NPDWR ViolationBack in compliance
- 2019-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1920 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2019-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1710 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2019-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 155.00 UG/L · limit 80.00 UG/LPeriod ended · no return to compliance on file
- 2018-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 172.00 UG/L · limit 80.00 UG/LPeriod ended · no return to compliance on file
- 2011-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 2006-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 2004-01-01Lead and Copper RuleInitial Tap Sampling for Pb and CuBack in compliance
System details
| Population served | 1,095 |
| Service connections | 365 |
| Water source | Groundwater |
| System type | Community Water System |
| Owner | Private |
| Status | Active |
| City | Sterlington |
| EPA ZIP on file | 71280 |
Areas served
- Union Parish
Reading this record
West Sterlington Water System is a community water system that draws from groundwater and serves about 1,095 people in Sterlington, Louisiana. Everything above comes from the EPA's Safe Drinking Water Information System (SDWIS), where states report every violation by every public water system.
Four kinds of violation. Only one is a measurement of the water: over the limit means a test came back above a legal maximum (an MCL). A treatment lapse means a required protective step was not done, such as disinfection, filtration, fixing a defect an inspector found, or filing a lead-pipe inventory. A missed or late test means a required test was skipped or never reported. That is the most common kind, and the most misread: it does not mean the water was bad, and it does not mean the water was fine. Notices and reports covers public notices and the annual Consumer Confidence Report.
Status. “Back in compliance” means the state recorded a return to compliance. “Period ended” means the violation's compliance period is over but no return to compliance was ever filed, which is common in older records. EPA's federal copy lags state records by months, so call the utility for anything current.