The record, year by year
Across Texas, 60% of violations are missed or late tests and 10% are water over a limit.
How far over the limit
Lead & copper at the tap
Utilities sample taps in homes most likely to have lead pipes, and report the 90th-percentile result: 9 in 10 homes sampled came in at or below this number. Above the red line (the action level) the utility must act. The action level is not a safe level; EPA's health goal for lead is zero. EPA's file does not date these results, so they are shown highest first.
Lead, 90th percentile 1 result on file · action level 15 ppb
Open now (2)
- 2022-04-22Public NoticePN Violation for NPDWR ViolationOpen
- 2020-10-14Public NoticePN Violation for NPDWR ViolationOpen
Every violation on record
- 2022-04-22Public NoticePN Violation for NPDWR ViolationOpen
- 2021-04-01ChlorineMonitoring and Reporting (DBP)Back in compliance
- 2021-03-04Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptBack in compliance
- 2021-03-01Surface water filtration (IESWTR)Monitoring, Turbidity (Enhanced SWTR)Period ended · no return to compliance on file
- 2021-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0960 MG/L · limit 0.0800 MG/LBack in compliance
- 2020-10-14Public NoticePN Violation for NPDWR ViolationOpen
- 2020-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1190 MG/L · limit 0.0800 MG/LBack in compliance
- 2020-10-01Revised Total Coliform RuleMONBack in compliance
- 2020-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1100 MG/L · limit 0.0800 MG/LBack in compliance
- 2020-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1320 MG/L · limit 0.0800 MG/LBack in compliance
- 2020-01-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0630 MG/L · limit 0.0600 MG/LBack in compliance
- 2020-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1460 MG/L · limit 0.0800 MG/LBack in compliance
- 2019-12-01Surface water filtration (IESWTR)Monthly Turbidity Exceed (Enhanced SWTR)Back in compliance
- 2019-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1450 MG/L · limit 0.0800 MG/LBack in compliance
- 2019-10-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0690 MG/L · limit 0.0600 MG/LBack in compliance
- 2019-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1480 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2019-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1690 MG/L · limit 0.0800 MG/LBack in compliance
- 2019-07-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0760 MG/L · limit 0.0600 MG/LBack in compliance
- 2019-04-01Total Haloacetic Acids (HAA5) ×2MCL, Averagemeasured 0.0680 MG/L · limit 0.0600 MG/LBack in compliance
- 2019-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1570 MG/L · limit 0.0800 MG/LBack in compliance
- 2019-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1440 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2019-01-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0610 MG/L · limit 0.0600 MG/LBack in compliance
- 2019-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1440 MG/L · limit 0.0800 MG/LBack in compliance
- 2018-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1390 MG/L · limit 0.0800 MG/LBack in compliance
- 2018-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1220 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
Show the other 52 entries
- 2018-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1210 MG/L · limit 0.0800 MG/LBack in compliance
- 2018-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1230 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2018-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1220 MG/L · limit 0.0800 MG/LBack in compliance
- 2017-10-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0640 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2017-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1270 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2017-07-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0790 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2017-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1360 MG/L · limit 0.0800 MG/LBack in compliance
- 2017-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1220 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2017-07-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0900 MG/L · limit 0.0600 MG/LBack in compliance
- 2017-04-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0890 MG/L · limit 0.0600 MG/LBack in compliance
- 2017-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1370 MG/L · limit 0.0800 MG/LBack in compliance
- 2017-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1210 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2017-04-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0730 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2017-01-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0790 MG/L · limit 0.0600 MG/LBack in compliance
- 2017-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1350 MG/L · limit 0.0800 MG/LBack in compliance
- 2016-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1290 MG/L · limit 0.0800 MG/LBack in compliance
- 2016-10-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0810 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2016-07-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0790 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2016-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1390 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2016-04-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0920 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2016-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1480 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2016-01-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0960 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2015-10-01Trihalomethanes (TTHM) ×2MCL, Averagemeasured 0.1690 MG/L · limit 0.0800 MG/LBack in compliance
- 2015-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1940 MG/L · limit 0.0800 MG/LBack in compliance
- 2015-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2010 MG/L · limit 0.0800 MG/LBack in compliance
- 2015-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.2030 MG/L · limit 0.0800 MG/LBack in compliance
- 2014-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1890 MG/L · limit 0.0800 MG/LBack in compliance
- 2014-09-26Public NoticePN Violation for NPDWR ViolationBack in compliance
- 2014-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1710 MG/L · limit 0.0800 MG/LBack in compliance
- 2014-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1220 MG/L · limit 0.0800 MG/LBack in compliance
- 2013-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1540 MG/L · limit 0.0800 MG/LBack in compliance
- 2013-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1140 MG/L · limit 0.0800 MG/LBack in compliance
- 2013-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1030 MG/L · limit 0.0800 MG/LBack in compliance
- 2012-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0900 MG/L · limit 0.0800 MG/LBack in compliance
- 2012-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0940 MG/L · limit 0.0800 MG/LBack in compliance
- 2012-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1140 MG/L · limit 0.0800 MG/LBack in compliance
- 2012-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1280 MG/L · limit 0.0800 MG/LBack in compliance
- 2011-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1190 MG/L · limit 0.0800 MG/LBack in compliance
- 2011-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1130 MG/L · limit 0.0800 MG/LBack in compliance
- 2011-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1160 MG/L · limit 0.0800 MG/LBack in compliance
- 2011-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1220 MG/L · limit 0.0800 MG/LBack in compliance
- 2010-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1230 MG/LBack in compliance
- 2010-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1200 MG/LBack in compliance
- 2010-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1120 MG/LBack in compliance
- 2010-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1190 MG/LBack in compliance
- 2009-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1190 MG/LBack in compliance
- 2009-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1240 MG/LBack in compliance
- 2009-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1351 MG/LBack in compliance
- 2009-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1420 MG/LBack in compliance
- 2008-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1530 MG/LBack in compliance
- 2008-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1750 MG/LBack in compliance
- 2006-09-01Public NoticePN Violation for NPDWR ViolationBack in compliance
System details
| Population served | 1,770 |
| Service connections | 734 |
| Water source | Surface Water Purchased |
| System type | Community Water System |
| Owner | Local Government |
| Status | Active |
| City | Wichita Falls |
| EPA ZIP on file | 76307-0240 |
Areas served
- Clay County
Reading this record
Rra Arrowhead Lake Lots is a community water system that draws from surface water purchased and serves about 1,770 people in Wichita Falls, Texas. Everything above comes from the EPA's Safe Drinking Water Information System (SDWIS), where states report every violation by every public water system.
Four kinds of violation. Only one is a measurement of the water: over the limit means a test came back above a legal maximum (an MCL). A treatment lapse means a required protective step was not done, such as disinfection, filtration, fixing a defect an inspector found, or filing a lead-pipe inventory. A missed or late test means a required test was skipped or never reported. That is the most common kind, and the most misread: it does not mean the water was bad, and it does not mean the water was fine. Notices and reports covers public notices and the annual Consumer Confidence Report.
Status. “Back in compliance” means the state recorded a return to compliance. “Period ended” means the violation's compliance period is over but no return to compliance was ever filed, which is common in older records. EPA's federal copy lags state records by months, so call the utility for anything current.