Patterson Town Hall (New)
On record since 2017: 21 violations. 21 over the limit. Most recent began 2023-01-01.
For this year's test results, ask the utility for its annual Consumer Confidence Report. Every community system must publish one.
More violations on record than 82% of active water systems in New York. Small systems with no staff chemist often rack up missed-test violations; big utilities rarely do.
The record, year by year
Across New York, 67% of violations are missed or late tests and 3% are water over a limit.
How far over the limit
Every violation on record
- 2023-01-01ChlorideMCL, Single Samplemeasured 414.00 MG/L · limit 250.00 MG/LBack in compliance
- 2022-10-01NitrateMCL, Single Samplemeasured 22.00 MG/L · limit 10.00 MG/LBack in compliance
- 2022-10-01ChlorideMCL, Single Samplemeasured 522.00 MG/L · limit 250.00 MG/LBack in compliance
- 2022-07-01Nitrate ×2MCL, Single Samplemeasured 20.10 MG/L · limit 10.00 MG/LBack in compliance
- 2022-04-01ChlorideMCL, Single Samplemeasured 553.00 MG/L · limit 250.00 MG/LBack in compliance
- 2022-04-01NitrateMCL, Single Samplemeasured 19.10 MG/L · limit 10.00 MG/LBack in compliance
- 2022-01-01ChlorideMCL, Single Samplemeasured 642.00 MG/L · limit 250.00 MG/LBack in compliance
- 2022-01-01NitrateMCL, Single Samplemeasured 18.40 MG/L · limit 10.00 MG/LBack in compliance
- 2021-10-01ChlorideMCL, Single Samplemeasured 556.00 MG/L · limit 250.00 MG/LBack in compliance
- 2021-10-01NitrateMCL, Single Samplemeasured 16.00 MG/L · limit 10.00 MG/LBack in compliance
- 2021-07-01NitrateMCL, Single Samplemeasured 17.10 MG/L · limit 10.00 MG/LBack in compliance
- 2021-07-01ChlorideMCL, Single Samplemeasured 616.00 MG/L · limit 250.00 MG/LBack in compliance
- 2019-07-01ChlorideMCL, Single Samplemeasured 564.00 MG/L · limit 250.00 MG/LBack in compliance
- 2019-04-01NitrateMCL, Single Samplemeasured 17.40 MG/LBack in compliance
- 2019-01-01ChlorideMCL, Single Samplemeasured 605.00 MG/L · limit 250.00 MG/LBack in compliance
- 2019-01-01NitrateMCL, Single Samplemeasured 16.20 MG/L · limit 10.00 MG/LBack in compliance
- 2018-12-17NitrateMCL, Single Samplemeasured 18.40 MG/L · limit 10.00 MG/LBack in compliance
- 2018-10-01NitrateMCL, Single Samplemeasured 35.60 MG/L · limit 10.00 MG/LBack in compliance
- 2018-01-01NitrateMCL, Single Samplemeasured 19.30 MG/L · limit 10.00 MG/LBack in compliance
- 2017-10-01NitrateMCL, Single Samplemeasured 17.10 MG/L · limit 10.00 MG/LBack in compliance
System details
| Population served | 25 |
| Service connections | 1 |
| Water source | Groundwater |
| System type | Transient Non-Community |
| Owner | Private |
| Status | Active |
| City | Patterson |
| EPA ZIP on file | 12563 |
Areas served
- Putnam County
Reading this record
Patterson Town Hall (New) is a transient non-community that draws from groundwater and serves about 25 people in Patterson, New York. Everything above comes from the EPA's Safe Drinking Water Information System (SDWIS), where states report every violation by every public water system.
Four kinds of violation. Only one is a measurement of the water: over the limit means a test came back above a legal maximum (an MCL). A treatment lapse means a required protective step was not done, such as disinfection, filtration, fixing a defect an inspector found, or filing a lead-pipe inventory. A missed or late test means a required test was skipped or never reported. That is the most common kind, and the most misread: it does not mean the water was bad, and it does not mean the water was fine. Notices and reports covers public notices and the annual Consumer Confidence Report.
Status. “Back in compliance” means the state recorded a return to compliance. “Period ended” means the violation's compliance period is over but no return to compliance was ever filed, which is common in older records. EPA's federal copy lags state records by months, so call the utility for anything current.