Nowata Co Rwd #2
A missed test is not evidence of bad water. It also is not evidence of good water: for that period nobody checked.
On record since 1979: 91 violations. 34 over the limit · 41 missed or late tests · 16 notices or reports. Most recent began 2025-07-01.
For this year's test results, ask the utility for its annual Consumer Confidence Report. Every community system must publish one.
More violations on record than 83% of active water systems in Oklahoma. Small systems with no staff chemist often rack up missed-test violations; big utilities rarely do.
The record, year by year
Across Oklahoma, 73% of violations are missed or late tests and 19% are water over a limit.
How far over the limit
Open now (38)
- 2025-07-01Consumer Confidence RuleCCR Complete Failure to ReportOpen
- 2025-07-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2025-05-11Public NoticePN Violation for NPDWR ViolationOpen
- 2025-04-01Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2025-02-13Public NoticePN Violation for NPDWR ViolationOpen
- 2025-01-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2024-12-30Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2024-10-22Public NoticePN Violation for NPDWR ViolationOpen
- 2024-10-10Public NoticePN Violation for NPDWR ViolationOpen
- 2024-07-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2024-06-30Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2024-06-05Public NoticePN Violation for NPDWR ViolationOpen
- 2024-03-31Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2024-03-20Public NoticePN Violation for NPDWR ViolationOpen
- 2024-01-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2023-12-30Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2023-12-16Public NoticePN Violation for NPDWR ViolationOpen
- 2023-10-01Public NoticePN Violation for NPDWR ViolationOpen
- 2023-09-29Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2023-07-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2023-06-30Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2023-04-01Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2023-01-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2022-12-30Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2022-07-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2022-01-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2021-07-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2021-04-01Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2021-01-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2020-12-30Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2020-09-29Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2020-06-30Total Haloacetic Acids (HAA5)Failure Submit IDSE/Subpart V Plan RptOpen
- 2020-06-30Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2020-03-31Total Haloacetic Acids (HAA5)Failure Submit IDSE/Subpart V Plan RptOpen
- 2020-03-31Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2019-12-30Total Haloacetic Acids (HAA5)Failure Submit IDSE/Subpart V Plan RptOpen
- 2019-12-30Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2018-10-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
Every violation on record
- 2025-07-01Consumer Confidence RuleCCR Complete Failure to ReportOpen
- 2025-07-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2025-05-11Public NoticePN Violation for NPDWR ViolationOpen
- 2025-04-01Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2025-02-13Public NoticePN Violation for NPDWR ViolationOpen
- 2025-01-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2025-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0870 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2024-12-30Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2024-10-22Public NoticePN Violation for NPDWR ViolationOpen
- 2024-10-10Public NoticePN Violation for NPDWR ViolationOpen
- 2024-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0890 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2024-07-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2024-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0810 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2024-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 2024-06-30Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2024-06-05Public NoticePN Violation for NPDWR ViolationOpen
- 2024-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0910 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2024-03-31Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2024-03-20Public NoticePN Violation for NPDWR ViolationOpen
- 2024-01-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2024-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1050 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2023-12-30Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2023-12-16Public NoticePN Violation for NPDWR ViolationOpen
- 2023-10-01Public NoticePN Violation for NPDWR ViolationOpen
- 2023-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1100 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
Show the other 66 entries
- 2023-09-29Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2023-07-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2023-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1150 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2023-06-30Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2023-04-01Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2023-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1040 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2023-01-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2023-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0970 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2022-12-30Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2022-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0920 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2022-07-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2022-01-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2021-07-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2021-04-01Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2021-01-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2021-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0810 MG/L · limit 0.0800 MG/LBack in compliance
- 2020-12-30Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2020-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0960 MG/L · limit 0.0800 MG/LBack in compliance
- 2020-09-29Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2020-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1000 MG/L · limit 0.0800 MG/LBack in compliance
- 2020-06-30Total Haloacetic Acids (HAA5)Failure Submit IDSE/Subpart V Plan RptOpen
- 2020-06-30Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2020-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1090 MG/L · limit 0.0800 MG/LBack in compliance
- 2020-03-31Total Haloacetic Acids (HAA5)Failure Submit IDSE/Subpart V Plan RptOpen
- 2020-03-31Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2020-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1120 MG/L · limit 0.0800 MG/LBack in compliance
- 2020-01-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0690 MG/L · limit 0.0600 MG/LBack in compliance
- 2019-12-30Total Haloacetic Acids (HAA5)Failure Submit IDSE/Subpart V Plan RptOpen
- 2019-12-30Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptOpen
- 2019-10-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0690 MG/L · limit 0.0600 MG/LBack in compliance
- 2019-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1120 MG/L · limit 0.0800 MG/LBack in compliance
- 2019-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1060 MG/L · limit 0.0800 MG/LBack in compliance
- 2019-07-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0660 MG/L · limit 0.0600 MG/LBack in compliance
- 2019-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0930 MG/L · limit 0.0800 MG/LBack in compliance
- 2019-04-01Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptBack in compliance
- 2019-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1060 MG/L · limit 0.0800 MG/LBack in compliance
- 2019-01-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0620 MG/L · limit 0.0600 MG/LBack in compliance
- 2018-10-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2018-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0960 MG/L · limit 0.0800 MG/LBack in compliance
- 2018-10-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0610 MG/L · limit 0.0600 MG/LBack in compliance
- 2018-09-29Total Haloacetic Acids (HAA5)Failure Submit IDSE/Subpart V Plan RptBack in compliance
- 2018-09-29Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptBack in compliance
- 2018-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1010 MG/L · limit 0.0800 MG/LBack in compliance
- 2018-07-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0640 MG/L · limit 0.0600 MG/LBack in compliance
- 2018-04-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0650 MG/L · limit 0.0600 MG/LBack in compliance
- 2018-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0880 MG/L · limit 0.0800 MG/LBack in compliance
- 2017-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 2015-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0850 MG/L · limit 0.0800 MG/LBack in compliance
- 2015-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0870 MG/L · limit 0.0800 MG/LBack in compliance
- 2014-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 2013-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 2012-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 2011-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 2010-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 1994-01-01Lead and Copper RuleInitial Tap Sampling for Pb and CuBack in compliance
- 1992-09-01Coliform (TCR)Monitoring, Routine Minor (TCR)Back in compliance
- 1992-08-01Coliform (TCR)Monitoring, Routine Minor (TCR)Back in compliance
- 1992-07-01Coliform (TCR)MCL, Monthly (TCR)Back in compliance
- 1992-04-01Coliform (TCR)Monitoring, Routine Minor (TCR)Back in compliance
- 1992-03-01Coliform (TCR)MCL, Monthly (TCR)Back in compliance
- 1986-09-01Coliform (Pre-TCR)MCL, Averagemeasured 9.00 Back in compliance
- 1985-01-01Coliform (Pre-TCR)Monitoring, RegularBack in compliance
- 1984-12-01Coliform (Pre-TCR)Monitoring, RegularBack in compliance
- 1983-07-31Coliform (Pre-TCR)Monitoring, RegularBack in compliance
- 1981-12-31Coliform (Pre-TCR)Monitoring, RegularBack in compliance
- 1979-10-31Coliform (Pre-TCR)Monitoring, RegularBack in compliance
System details
| Population served | 205 |
| Service connections | 82 |
| Water source | Surface Water Purchased |
| System type | Community Water System |
| Owner | Local Government |
| Status | Active |
| City | Nowata |
| EPA ZIP on file | 74048 |
Areas served
- Nowata County
Reading this record
Nowata Co Rwd #2 is a community water system that draws from surface water purchased and serves about 205 people in Nowata, Oklahoma. Everything above comes from the EPA's Safe Drinking Water Information System (SDWIS), where states report every violation by every public water system.
Four kinds of violation. Only one is a measurement of the water: over the limit means a test came back above a legal maximum (an MCL). A treatment lapse means a required protective step was not done, such as disinfection, filtration, fixing a defect an inspector found, or filing a lead-pipe inventory. A missed or late test means a required test was skipped or never reported. That is the most common kind, and the most misread: it does not mean the water was bad, and it does not mean the water was fine. Notices and reports covers public notices and the annual Consumer Confidence Report.
Status. “Back in compliance” means the state recorded a return to compliance. “Period ended” means the violation's compliance period is over but no return to compliance was ever filed, which is common in older records. EPA's federal copy lags state records by months, so call the utility for anything current.