Las Vegas (City Of)
On record since 2006: 76 violations. 11 over the limit · 29 treatment lapses · 23 missed or late tests · 13 notices or reports. Most recent began 2025-02-01.
For this year's test results, ask the utility for its annual Consumer Confidence Report. Every community system must publish one.
More violations on record than 91% of active water systems in New Mexico. Small systems with no staff chemist often rack up missed-test violations; big utilities rarely do.
The record, year by year
Across New Mexico, 40% of violations are missed or late tests and 6% are water over a limit.
How far over the limit
Lead & copper at the tap
Utilities sample taps in homes most likely to have lead pipes, and report the 90th-percentile result: 9 in 10 homes sampled came in at or below this number. Above the red line (the action level) the utility must act. The action level is not a safe level; EPA's health goal for lead is zero. EPA's file does not date these results, so they are shown highest first.
Lead, 90th percentile 3 results on file · action level 15 ppb
Every violation on record
- 2025-02-01Surface water filtration (IESWTR)Single Turbidity Exceed (Enhanced SWTR)Period ended · no return to compliance on file
- 2025-01-01Surface water treatment (SWTR)Monitoring of Treatment (SWTR-Filter)Period ended · no return to compliance on file
- 2024-10-01Carbon, TotalTreatment Technique Precursor Removalmeasured 0.9100 RATIO · limit 1.00 RATIOPeriod ended · no return to compliance on file
- 2024-10-01Surface water filtration (IESWTR)Monitoring, Turbidity (Enhanced SWTR)Back in compliance
- 2024-10-01Surface water treatment (SWTR)Monitoring of Treatment (SWTR-Filter)Back in compliance
- 2024-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0870 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2024-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0900 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2024-07-01Carbon, Total ×3Treatment Technique Precursor Removalmeasured 0.9200 RATIOBack in compliance
- 2024-04-01Carbon, TotalTreatment Technique Precursor Removalmeasured 0.8300 RATIOPeriod ended · no return to compliance on file
- 2024-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0850 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2024-01-01Carbon, Total ×3Treatment Technique Precursor Removalmeasured 0.8400 RATIO · limit 1.00 RATIOPeriod ended · no return to compliance on file
- 2024-01-01Trihalomethanes (TTHM) ×2MCL, Averagemeasured 0.0900 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2023-12-01Surface water filtration (IESWTR)Single Turbidity Exceed (Enhanced SWTR)Back in compliance
- 2023-11-23Public NoticePN Violation for NPDWR ViolationBack in compliance
- 2023-11-01Surface water filtration (IESWTR)Single Turbidity Exceed (Enhanced SWTR)Back in compliance
- 2023-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0820 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2023-10-01Carbon, Total ×3Treatment Technique Precursor Removalmeasured 0.8500 RATIOPeriod ended · no return to compliance on file
- 2023-07-01Carbon, Total ×3Treatment Technique Precursor Removalmeasured 0.8800 RATIO · limit 1.00 RATIOPeriod ended · no return to compliance on file
- 2023-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0850 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2023-05-07Surface water filtration (IESWTR)Failure Submit Filter Profile/CPE ReportBack in compliance
- 2023-04-01Carbon, Total ×3Treatment Technique Precursor Removalmeasured 0.7300 RATIOPeriod ended · no return to compliance on file
- 2023-04-01Trihalomethanes (TTHM) ×3MCL, Averagemeasured 0.0810 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2023-03-08Surface water filtration (IESWTR)Failure Submit Filter Profile/CPE ReportBack in compliance
- 2023-03-01Surface water treatment (SWTR)Treatment Technique (SWTR and GWR)Back in compliance
- 2023-03-01Surface water filtration (IESWTR)Single Turbidity Exceed (Enhanced SWTR)Back in compliance
Show the other 37 entries
- 2023-02-01Surface water filtration (IESWTR)Single Turbidity Exceed (Enhanced SWTR)Back in compliance
- 2023-02-01Surface water filtration (IESWTR)Monthly Turbidity Exceed (Enhanced SWTR)Back in compliance
- 2023-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0830 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2023-01-01Surface water filtration (IESWTR)Single Turbidity Exceed (Enhanced SWTR)Back in compliance
- 2022-03-01Surface water treatment (SWTR)Monitoring of Treatment (SWTR-Filter)Back in compliance
- 2022-02-01Surface water treatment (SWTR)Monitoring of Treatment (SWTR-Filter)Back in compliance
- 2022-01-01Carbon, Total ×2Treatment Technique Precursor Removalmeasured 0.9100 RATIOBack in compliance
- 2021-12-18Public NoticePN Violation for NPDWR ViolationBack in compliance
- 2021-10-01Surface water treatment (SWTR)Monitoring of Treatment (SWTR-Filter)Period ended · no return to compliance on file
- 2021-06-24Public NoticePN Violation for NPDWR ViolationBack in compliance
- 2021-06-01Total Haloacetic Acids (HAA5)Monitoring and Reporting (DBP)Back in compliance
- 2021-06-01Trihalomethanes (TTHM)Monitoring and Reporting (DBP)Back in compliance
- 2021-04-01Groundwater RuleFailure to Notify Other PWSBack in compliance
- 2021-04-01Surface water treatment (SWTR)Treatment Technique (SWTR and GWR)Back in compliance
- 2021-02-01Surface water treatment (SWTR)Monitoring of Treatment (SWTR-Filter)Back in compliance
- 2020-09-25Public NoticePN Violation for NPDWR ViolationBack in compliance
- 2020-01-01Revised Total Coliform RuleMONBack in compliance
- 2019-08-01Surface water treatment (SWTR)Monitoring of Treatment (SWTR-Filter)Back in compliance
- 2019-04-01Groundwater RuleFailure to Notify Other PWSBack in compliance
- 2019-03-01Total Haloacetic Acids (HAA5)Monitoring and Reporting (DBP)Back in compliance
- 2019-03-01Trihalomethanes (TTHM)Monitoring and Reporting (DBP)Back in compliance
- 2018-12-01Total Haloacetic Acids (HAA5)Monitoring and Reporting (DBP)Back in compliance
- 2018-12-01Trihalomethanes (TTHM)Monitoring and Reporting (DBP)Back in compliance
- 2017-04-01Groundwater RuleFailure to Notify Other PWSBack in compliance
- 2016-12-18Public NoticePN Violation for NPDWR ViolationBack in compliance
- 2016-06-02Revised Total Coliform RuleOtherBack in compliance
- 2016-06-01Revised Total Coliform RuleMONBack in compliance
- 2015-09-01Total Haloacetic Acids (HAA5)Monitoring and Reporting (DBP)Back in compliance
- 2015-09-01Trihalomethanes (TTHM)Monitoring and Reporting (DBP)Back in compliance
- 2015-06-01Total Haloacetic Acids (HAA5)Monitoring and Reporting (DBP)Back in compliance
- 2015-06-01Trihalomethanes (TTHM)Monitoring and Reporting (DBP)Back in compliance
- 2012-10-01Consumer Confidence RuleCCR Inadequate ReportingBack in compliance
- 2010-11-04Public NoticePN Violation for NPDWR ViolationBack in compliance
- 2010-10-01Surface water treatment (LT2)Failure Submit Treatment Requirement RptBack in compliance
- 2010-01-02Dbp Stage 2Failure Submit IDSE/Subpart V Plan RptBack in compliance
- 2008-11-28Public NoticePN Violation for NPDWR ViolationBack in compliance
- 2006-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
System details
| Population served | 14,530 |
| Service connections | 6,458 |
| Water source | Surface Water |
| System type | Community Water System |
| Owner | Local Government |
| Status | Active |
| City | Las Vegas |
| EPA ZIP on file | 87701 |
Areas served
- Las Vegas, San Miguel County
Reading this record
Las Vegas (City Of) is a community water system that draws from surface water and serves about 14,530 people in Las Vegas, New Mexico. Everything above comes from the EPA's Safe Drinking Water Information System (SDWIS), where states report every violation by every public water system.
Four kinds of violation. Only one is a measurement of the water: over the limit means a test came back above a legal maximum (an MCL). A treatment lapse means a required protective step was not done, such as disinfection, filtration, fixing a defect an inspector found, or filing a lead-pipe inventory. A missed or late test means a required test was skipped or never reported. That is the most common kind, and the most misread: it does not mean the water was bad, and it does not mean the water was fine. Notices and reports covers public notices and the annual Consumer Confidence Report.
Status. “Back in compliance” means the state recorded a return to compliance. “Period ended” means the violation's compliance period is over but no return to compliance was ever filed, which is common in older records. EPA's federal copy lags state records by months, so call the utility for anything current.