Guatay Mutual Benefit Corporation
A missed test is not evidence of bad water. It also is not evidence of good water: for that period nobody checked.
On record since 1993: 56 violations. 47 over the limit · 9 missed or late tests. Most recent began 2023-10-01.
For this year's test results, ask the utility for its annual Consumer Confidence Report. Every community system must publish one.
More violations on record than 98% of active water systems in California. Small systems with no staff chemist often rack up missed-test violations; big utilities rarely do.
The record, year by year
Across California, 52% of violations are missed or late tests and 29% are water over a limit.
How far over the limit
Lead & copper at the tap
Utilities sample taps in homes most likely to have lead pipes, and report the 90th-percentile result: 9 in 10 homes sampled came in at or below this number. Above the red line (the action level) the utility must act. The action level is not a safe level; EPA's health goal for lead is zero. EPA's file does not date these results, so they are shown highest first.
Lead, 90th percentile 2 results on file · action level 15 ppb
Open now (1)
- 2021-10-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
Every violation on record
- 2023-10-01Combined Uranium ×2MCL, Single Samplemeasured 71.00 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2023-07-01Combined Uranium ×2MCL, Single Samplemeasured 130.00 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2023-01-01NitrateMonitoring, RegularPeriod ended · no return to compliance on file
- 2023-01-01Combined Uranium ×3MCL, Single Samplemeasured 55.00 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2022-10-01Combined Uranium ×3MCL, Single Samplemeasured 80.00 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2022-07-01Combined Uranium ×3MCL, Single Samplemeasured 49.00 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2022-01-01Combined Uranium ×2MCL, Single Samplemeasured 130.00 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2022-01-01Combined UraniumMCL, Averagemeasured 40.00 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2021-10-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2021-10-01Combined Uranium ×2MCL, Single Samplemeasured 42.00 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2021-10-01Combined UraniumMCL, Averagemeasured 44.20 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2021-04-01Combined Uranium ×2MCL, Single Samplemeasured 40.60 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2021-04-01Combined UraniumMCL, Averagemeasured 128.00 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2021-01-01Combined Uranium ×2MCL, Averagemeasured 37.70 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2020-10-01Combined Uranium ×2MCL, Averagemeasured 32.70 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2020-07-01Combined UraniumMCL, Averagemeasured 30.43 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2020-04-01Combined UraniumMCL, Averagemeasured 90.10 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2019-10-01Combined Uranium ×2MCL, Averagemeasured 53.00 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2019-04-01Combined Uranium ×3MCL, Averagemeasured 26.80 PCI/LPeriod ended · no return to compliance on file
- 2019-01-01Combined Uranium ×2MCL, Averagemeasured 93.60 PCI/LPeriod ended · no return to compliance on file
- 2018-10-01Combined Uranium ×2MCL, Averagemeasured 83.60 PCI/LPeriod ended · no return to compliance on file
- 2018-07-01Combined UraniumMCL, Averagemeasured 57.90 PCI/LPeriod ended · no return to compliance on file
- 2018-04-01Combined UraniumMCL, Averagemeasured 49.65 PCI/L · limit 30.00 PCI/LPeriod ended · no return to compliance on file
- 2018-01-01Combined UraniumMCL, Averagemeasured 41.03 PCI/L · limit 30.00 PCI/LPeriod ended · no return to compliance on file
- 2017-10-01Combined UraniumMCL, Averagemeasured 54.30 PCI/L · limit 30.00 PCI/LPeriod ended · no return to compliance on file
Show the other 13 entries
- 2017-07-01Combined UraniumMCL, Averagemeasured 49.18 PCI/L · limit 30.00 PCI/LPeriod ended · no return to compliance on file
- 2017-04-01Combined UraniumMCL, Averagemeasured 24.78 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2017-01-01Combined UraniumMCL, Averagemeasured 24.93 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2016-10-01Combined UraniumMCL, Averagemeasured 22.50 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2016-07-01Combined UraniumMCL, Averagemeasured 21.60 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2016-04-01Combined UraniumMCL, Averagemeasured 24.00 PCI/L · limit 20.00 PCI/LPeriod ended · no return to compliance on file
- 2016-01-01BenzeneMonitoring, RegularBack in compliance
- 2016-01-01Methyl Tert-Butyl EtherMonitoring, RegularPeriod ended · no return to compliance on file
- 2016-01-01TdsMonitoring, RegularPeriod ended · no return to compliance on file
- 2016-01-01OdorMonitoring, RegularPeriod ended · no return to compliance on file
- 2016-01-01ManganeseMonitoring, RegularPeriod ended · no return to compliance on file
- 2016-01-01IronMonitoring, RegularPeriod ended · no return to compliance on file
- 1993-07-01Lead and Copper RuleInitial Tap Sampling for Pb and CuBack in compliance
System details
| Population served | 100 |
| Service connections | 32 |
| Water source | Groundwater |
| System type | Community Water System |
| Owner | Private |
| Status | Active |
| City | Guatay |
| EPA ZIP on file | 91931 |
Areas served
- San Diego County
Reading this record
Guatay Mutual Benefit Corporation is a community water system that draws from groundwater and serves about 100 people in Guatay, California. Everything above comes from the EPA's Safe Drinking Water Information System (SDWIS), where states report every violation by every public water system.
Four kinds of violation. Only one is a measurement of the water: over the limit means a test came back above a legal maximum (an MCL). A treatment lapse means a required protective step was not done, such as disinfection, filtration, fixing a defect an inspector found, or filing a lead-pipe inventory. A missed or late test means a required test was skipped or never reported. That is the most common kind, and the most misread: it does not mean the water was bad, and it does not mean the water was fine. Notices and reports covers public notices and the annual Consumer Confidence Report.
Status. “Back in compliance” means the state recorded a return to compliance. “Period ended” means the violation's compliance period is over but no return to compliance was ever filed, which is common in older records. EPA's federal copy lags state records by months, so call the utility for anything current.