Golden State Water Company - South Shore
A missed test is not evidence of bad water. It also is not evidence of good water: for that period nobody checked.
On record since 1999: 33 violations. 27 over the limit · 1 treatment lapse · 5 missed or late tests. Most recent began 2023-07-01.
For this year's test results, ask the utility for its annual Consumer Confidence Report. Every community system must publish one.
More violations on record than 96% of active water systems in California. Small systems with no staff chemist often rack up missed-test violations; big utilities rarely do.
The record, year by year
Across California, 52% of violations are missed or late tests and 29% are water over a limit.
How far over the limit
Lead & copper at the tap
Utilities sample taps in homes most likely to have lead pipes, and report the 90th-percentile result: 9 in 10 homes sampled came in at or below this number. Above the red line (the action level) the utility must act. The action level is not a safe level; EPA's health goal for lead is zero. EPA's file does not date these results, so they are shown highest first.
Lead, 90th percentile 3 results on file · action level 15 ppb
Open now (1)
- 2020-10-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
Every violation on record
- 2023-07-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 87.17 UG/L · limit 60.00 UG/LPeriod ended · no return to compliance on file
- 2023-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 112.30 UG/L · limit 80.00 UG/LPeriod ended · no return to compliance on file
- 2023-04-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 112.31 UG/L · limit 60.00 UG/LPeriod ended · no return to compliance on file
- 2023-01-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 110.44 UG/L · limit 60.00 UG/LPeriod ended · no return to compliance on file
- 2022-10-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 99.26 UG/L · limit 60.00 UG/LPeriod ended · no return to compliance on file
- 2022-07-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 85.47 UG/L · limit 60.00 UG/LPeriod ended · no return to compliance on file
- 2022-04-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 86.00 UG/L · limit 60.00 UG/LPeriod ended · no return to compliance on file
- 2022-01-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 83.65 UG/L · limit 60.00 UG/LPeriod ended · no return to compliance on file
- 2021-04-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0820 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2021-01-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0860 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2020-10-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/ROpen
- 2020-10-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0780 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2020-04-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0785 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2020-01-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0790 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2019-10-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0848 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2019-07-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0935 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2019-04-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.1010 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2019-01-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 124.30 UG/LPeriod ended · no return to compliance on file
- 2018-10-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 137.00 UG/LPeriod ended · no return to compliance on file
- 2018-07-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 147.50 UG/LPeriod ended · no return to compliance on file
- 2018-04-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 140.00 UG/LPeriod ended · no return to compliance on file
- 2018-01-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 101.10 UG/LPeriod ended · no return to compliance on file
- 2017-10-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 83.23 UG/LPeriod ended · no return to compliance on file
- 2017-07-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 65.93 UG/LPeriod ended · no return to compliance on file
- 2016-10-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0760 MG/L · limit 0.0600 MG/LBack in compliance
Show the other 8 entries
- 2016-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0970 MG/L · limit 0.0800 MG/LBack in compliance
- 2016-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 108.00 UG/L · limit 80.00 UG/LBack in compliance
- 2016-04-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 71.00 UG/L · limit 60.00 UG/LBack in compliance
- 2011-01-01Trihalomethanes (TTHM)Monitoring and Reporting (DBP)Back in compliance
- 2011-01-01Total Haloacetic Acids (HAA5)Monitoring and Reporting (DBP)Back in compliance
- 2009-01-01Trihalomethanes (TTHM)Monitoring and Reporting (DBP)Back in compliance
- 2009-01-01Total Haloacetic Acids (HAA5)Monitoring and Reporting (DBP)Back in compliance
- 1999-09-01Surface water treatment (SWTR)Treatment Technique (SWTR and GWR)Back in compliance
System details
| Population served | 30 |
| Service connections | 24 |
| Water source | Surface Water |
| System type | Community Water System |
| Owner | Private |
| Status | Active |
| City | Rancho Cordova |
| EPA ZIP on file | 95670 |
Areas served
- Lake County
Reading this record
Golden State Water Company - South Shore is a community water system that draws from surface water and serves about 30 people in Rancho Cordova, California. Everything above comes from the EPA's Safe Drinking Water Information System (SDWIS), where states report every violation by every public water system.
Four kinds of violation. Only one is a measurement of the water: over the limit means a test came back above a legal maximum (an MCL). A treatment lapse means a required protective step was not done, such as disinfection, filtration, fixing a defect an inspector found, or filing a lead-pipe inventory. A missed or late test means a required test was skipped or never reported. That is the most common kind, and the most misread: it does not mean the water was bad, and it does not mean the water was fine. Notices and reports covers public notices and the annual Consumer Confidence Report.
Status. “Back in compliance” means the state recorded a return to compliance. “Period ended” means the violation's compliance period is over but no return to compliance was ever filed, which is common in older records. EPA's federal copy lags state records by months, so call the utility for anything current.