Farmington Pws
On record since 2009: 45 violations. 39 over the limit · 2 missed or late tests · 4 notices or reports. Most recent began 2024-10-01.
For this year's test results, ask the utility for its annual Consumer Confidence Report. Every community system must publish one.
More violations on record than 95% of active water systems in Missouri. Small systems with no staff chemist often rack up missed-test violations; big utilities rarely do.
The record, year by year
Across Missouri, 54% of violations are missed or late tests and 8% are water over a limit.
How far over the limit
Lead & copper at the tap
Utilities sample taps in homes most likely to have lead pipes, and report the 90th-percentile result: 9 in 10 homes sampled came in at or below this number. Above the red line (the action level) the utility must act. The action level is not a safe level; EPA's health goal for lead is zero. EPA's file does not date these results, so they are shown highest first.
Lead, 90th percentile 8 results on file · action level 15 ppb
Every violation on record
- 2024-10-01Combined Radium (-226 and -228)MCL, Averagemeasured 5.53 PCI/L · limit 5.00 PCI/LPeriod ended · no return to compliance on file
- 2024-07-01Combined Radium (-226 and -228)MCL, Averagemeasured 5.83 PCI/L · limit 5.00 PCI/LPeriod ended · no return to compliance on file
- 2022-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 2021-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 2015-11-01Coliform (TCR)MCL, Monthly (TCR)Back in compliance
- 2015-10-01Coliform (TCR)MCL, Monthly (TCR)Back in compliance
- 2015-09-01Coliform (TCR)MCL, Monthly (TCR)Back in compliance
- 2015-09-01E. ColiMonitoring, Source Water (GWR)Back in compliance
- 2015-08-01Coliform (TCR)MCL, Monthly (TCR)Back in compliance
- 2014-01-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 16.37 PCI/L · limit 15.00 PCI/LBack in compliance
- 2013-10-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 15.90 PCI/L · limit 15.00 PCI/LBack in compliance
- 2013-07-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 17.43 PCI/L · limit 15.00 PCI/LBack in compliance
- 2013-04-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 18.23 PCI/L · limit 15.00 PCI/LBack in compliance
- 2013-04-01Combined Radium (-226 and -228)MCL, Averagemeasured 6.48 PCI/L · limit 5.00 PCI/LBack in compliance
- 2013-01-01Combined Radium (-226 and -228)MCL, Averagemeasured 6.05 PCI/L · limit 5.00 PCI/LBack in compliance
- 2012-12-31Public NoticePN Violation for NPDWR ViolationBack in compliance
- 2012-11-01E. ColiMonitoring, Source Water (GWR)Back in compliance
- 2012-10-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 15.95 PCI/L · limit 5.00 PCI/LBack in compliance
- 2012-10-01Combined Radium (-226 and -228)MCL, Averagemeasured 6.20 PCI/L · limit 5.00 PCI/LBack in compliance
- 2012-07-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 17.80 PCI/L · limit 15.00 PCI/LBack in compliance
- 2012-07-01Combined Radium (-226 and -228)MCL, Averagemeasured 5.68 PCI/L · limit 5.00 PCI/LBack in compliance
- 2012-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 2012-04-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 18.00 PCI/L · limit 15.00 PCI/LBack in compliance
- 2012-01-01Combined Radium (-226 and -228)MCL, Averagemeasured 6.05 PCI/L · limit 5.00 PCI/LBack in compliance
- 2012-01-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 18.04 PCI/L · limit 15.00 PCI/LBack in compliance
Show the other 20 entries
- 2011-10-01Combined Radium (-226 and -228)MCL, Averagemeasured 7.00 PCI/L · limit 5.00 PCI/LBack in compliance
- 2011-10-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 19.43 PCI/L · limit 15.00 PCI/LBack in compliance
- 2011-07-01Combined Radium (-226 and -228)MCL, Averagemeasured 9.24 PCI/L · limit 5.00 PCI/LBack in compliance
- 2011-07-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 22.23 PCI/L · limit 15.00 PCI/LBack in compliance
- 2011-04-01Combined Radium (-226 and -228)MCL, Averagemeasured 12.54 PCI/L · limit 5.00 PCI/LBack in compliance
- 2011-04-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 25.86 PCI/L · limit 15.00 PCI/LBack in compliance
- 2011-01-01Combined Radium (-226 and -228)MCL, Averagemeasured 15.62 PCI/L · limit 5.00 PCI/LBack in compliance
- 2011-01-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 31.05 PCI/L · limit 15.00 PCI/LBack in compliance
- 2010-10-01Combined Radium (-226 and -228)MCL, Averagemeasured 19.93 PCI/L · limit 5.00 PCI/LBack in compliance
- 2010-10-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 36.50 PCI/L · limit 15.00 PCI/LBack in compliance
- 2010-07-01Combined Radium (-226 and -228)MCL, Averagemeasured 19.95 PCI/L · limit 5.00 PCI/LBack in compliance
- 2010-07-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 36.25 PCI/L · limit 15.00 PCI/LBack in compliance
- 2010-04-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 39.55 PCI/L · limit 15.00 PCI/LBack in compliance
- 2010-04-01Combined Radium (-226 and -228)MCL, Averagemeasured 19.85 PCI/L · limit 5.00 PCI/LBack in compliance
- 2010-01-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 28.95 PCI/L · limit 15.00 PCI/LBack in compliance
- 2010-01-01Combined Radium (-226 and -228)MCL, Averagemeasured 15.60 PCI/L · limit 5.00 PCI/LBack in compliance
- 2009-10-01Combined Radium (-226 and -228)MCL, Averagemeasured 15.10 PCI/LBack in compliance
- 2009-10-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 29.29 PCI/LBack in compliance
- 2009-07-01Combined Radium (-226 and -228)MCL, Averagemeasured 22.23 PCI/LBack in compliance
- 2009-07-01Gross Alpha, Excl. Radon and UMCL, Averagemeasured 43.14 PCI/LBack in compliance
System details
| Population served | 18,217 |
| Service connections | 6,178 |
| Water source | Groundwater |
| System type | Community Water System |
| Owner | Local Government |
| Status | Active |
| City | Farmington |
| EPA ZIP on file | 63640-0000 |
Areas served
- Farmington, St. Francois County
Reading this record
Farmington Pws is a community water system that draws from groundwater and serves about 18,217 people in Farmington, Missouri. Everything above comes from the EPA's Safe Drinking Water Information System (SDWIS), where states report every violation by every public water system.
Four kinds of violation. Only one is a measurement of the water: over the limit means a test came back above a legal maximum (an MCL). A treatment lapse means a required protective step was not done, such as disinfection, filtration, fixing a defect an inspector found, or filing a lead-pipe inventory. A missed or late test means a required test was skipped or never reported. That is the most common kind, and the most misread: it does not mean the water was bad, and it does not mean the water was fine. Notices and reports covers public notices and the annual Consumer Confidence Report.
Status. “Back in compliance” means the state recorded a return to compliance. “Period ended” means the violation's compliance period is over but no return to compliance was ever filed, which is common in older records. EPA's federal copy lags state records by months, so call the utility for anything current.