Dubach Water System
On record since 2004: 59 violations. 36 over the limit · 18 missed or late tests · 5 notices or reports. Most recent began 2025-07-01.
For this year's test results, ask the utility for its annual Consumer Confidence Report. Every community system must publish one.
More violations on record than 95% of active water systems in Louisiana. Small systems with no staff chemist often rack up missed-test violations; big utilities rarely do.
The record, year by year
Across Louisiana, 31% of violations are missed or late tests and 25% are water over a limit.
How far over the limit
Lead & copper at the tap
Utilities sample taps in homes most likely to have lead pipes, and report the 90th-percentile result: 9 in 10 homes sampled came in at or below this number. Above the red line (the action level) the utility must act. The action level is not a safe level; EPA's health goal for lead is zero. EPA's file does not date these results, so they are shown highest first.
Lead, 90th percentile 3 results on file · action level 15 ppb
Every violation on record
- 2025-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1510 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2025-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1560 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2025-02-12Public NoticePN Violation for NPDWR ViolationBack in compliance
- 2025-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1530 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2024-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1560 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2024-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1590 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2024-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1490 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2024-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1380 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2023-11-09Public NoticePN Violation for NPDWR ViolationBack in compliance
- 2023-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1200 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2023-08-05Public NoticePN Violation for NPDWR ViolationBack in compliance
- 2023-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.1050 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2023-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0970 MG/L · limit 0.0800 MG/LPeriod ended · no return to compliance on file
- 2021-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0810 MG/L · limit 0.0800 MG/LBack in compliance
- 2021-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0850 MG/L · limit 0.0800 MG/LBack in compliance
- 2021-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0890 MG/L · limit 0.0800 MG/LBack in compliance
- 2020-12-10Lead and Copper RuleLead Consumer NoticeBack in compliance
- 2020-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0950 MG/L · limit 0.0800 MG/LBack in compliance
- 2020-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0870 MG/L · limit 0.0800 MG/LBack in compliance
- 2020-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 0.0880 MG/L · limit 0.0800 MG/LBack in compliance
- 2019-10-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/RBack in compliance
- 2018-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 87.00 UG/L · limit 80.00 UG/LBack in compliance
- 2018-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 82.00 UG/L · limit 80.00 UG/LBack in compliance
- 2017-10-31Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptBack in compliance
- 2017-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 209.00 UG/L · limit 80.00 UG/LBack in compliance
Show the other 34 entries
- 2017-10-01Consumer Confidence RuleCCR Inadequate ReportingBack in compliance
- 2017-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 164.00 UG/L · limit 80.00 UG/LBack in compliance
- 2017-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 166.00 UG/L · limit 80.00 UG/LBack in compliance
- 2017-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 157.00 UG/L · limit 80.00 UG/LBack in compliance
- 2016-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 125.00 UG/L · limit 80.00 UG/LBack in compliance
- 2016-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 155.00 UG/L · limit 80.00 UG/LBack in compliance
- 2016-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 180.00 UG/L · limit 80.00 UG/LBack in compliance
- 2016-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 203.00 UG/L · limit 80.00 UG/LBack in compliance
- 2015-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 219.00 UG/L · limit 80.00 UG/LBack in compliance
- 2015-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 210.00 UG/L · limit 80.00 UG/LBack in compliance
- 2015-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 195.00 UG/L · limit 80.00 UG/LBack in compliance
- 2015-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 204.00 UG/L · limit 80.00 UG/LBack in compliance
- 2014-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 212.00 UG/L · limit 80.00 UG/LBack in compliance
- 2014-07-31Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptBack in compliance
- 2014-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 222.00 UG/L · limit 80.00 UG/LBack in compliance
- 2014-05-01Trihalomethanes (TTHM)Failure Submit IDSE/Subpart V Plan RptBack in compliance
- 2014-04-01Trihalomethanes (TTHM)MCL, Averagemeasured 296.00 UG/L · limit 80.00 UG/LBack in compliance
- 2014-01-01Trihalomethanes (TTHM)MCL, Averagemeasured 300.00 UG/L · limit 80.00 UG/LBack in compliance
- 2013-10-01Trihalomethanes (TTHM)MCL, Averagemeasured 229.00 UG/L · limit 80.00 UG/LBack in compliance
- 2013-10-01Total Haloacetic Acids (HAA5)Monitoring and Reporting (DBP)Back in compliance
- 2013-10-01Trihalomethanes (TTHM)Monitoring and Reporting (DBP)Back in compliance
- 2013-07-01Trihalomethanes (TTHM)MCL, Averagemeasured 172.00 UG/L · limit 80.00 UG/LBack in compliance
- 2012-06-29Public NoticePN Violation for NPDWR ViolationBack in compliance
- 2011-07-01Total Haloacetic Acids (HAA5)Monitoring and Reporting (DBP)Back in compliance
- 2011-07-01Trihalomethanes (TTHM)Monitoring and Reporting (DBP)Back in compliance
- 2010-07-02Dbp Stage 2Failure Submit IDSE/Subpart V Plan RptBack in compliance
- 2010-07-01Total Haloacetic Acids (HAA5)Monitoring and Reporting (DBP)Back in compliance
- 2010-07-01Trihalomethanes (TTHM)Monitoring and Reporting (DBP)Back in compliance
- 2010-01-01Total Haloacetic Acids (HAA5)Monitoring and Reporting (DBP)Back in compliance
- 2010-01-01Trihalomethanes (TTHM)Monitoring and Reporting (DBP)Back in compliance
- 2009-10-01Total Haloacetic Acids (HAA5)Monitoring and Reporting (DBP)Back in compliance
- 2009-10-01Trihalomethanes (TTHM)Monitoring and Reporting (DBP)Back in compliance
- 2009-07-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/RBack in compliance
- 2004-01-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/RBack in compliance
System details
| Population served | 1,218 |
| Service connections | 406 |
| Water source | Groundwater |
| System type | Community Water System |
| Owner | Local Government |
| Status | Active |
| City | Dubach |
| EPA ZIP on file | 71235 |
Areas served
- Lincoln Parish
Reading this record
Dubach Water System is a community water system that draws from groundwater and serves about 1,218 people in Dubach, Louisiana. Everything above comes from the EPA's Safe Drinking Water Information System (SDWIS), where states report every violation by every public water system.
Four kinds of violation. Only one is a measurement of the water: over the limit means a test came back above a legal maximum (an MCL). A treatment lapse means a required protective step was not done, such as disinfection, filtration, fixing a defect an inspector found, or filing a lead-pipe inventory. A missed or late test means a required test was skipped or never reported. That is the most common kind, and the most misread: it does not mean the water was bad, and it does not mean the water was fine. Notices and reports covers public notices and the annual Consumer Confidence Report.
Status. “Back in compliance” means the state recorded a return to compliance. “Period ended” means the violation's compliance period is over but no return to compliance was ever filed, which is common in older records. EPA's federal copy lags state records by months, so call the utility for anything current.