Del Oro River Island Serv Terr #2
On record since 1997: 46 violations. 37 over the limit · 8 missed or late tests · 1 notice or report. Most recent began 2024-08-01.
For this year's test results, ask the utility for its annual Consumer Confidence Report. Every community system must publish one.
More violations on record than 97% of active water systems in California. Small systems with no staff chemist often rack up missed-test violations; big utilities rarely do.
The record, year by year
Across California, 52% of violations are missed or late tests and 29% are water over a limit.
How far over the limit
Lead & copper at the tap
Utilities sample taps in homes most likely to have lead pipes, and report the 90th-percentile result: 9 in 10 homes sampled came in at or below this number. Above the red line (the action level) the utility must act. The action level is not a safe level; EPA's health goal for lead is zero. EPA's file does not date these results, so they are shown highest first.
Lead, 90th percentile 4 results on file · action level 15 ppb
Every violation on record
- 2024-08-01Revised Total Coliform RuleMONBack in compliance
- 2020-10-01Combined UraniumMCL, Averagemeasured 37.00 PCI/L · limit 20.00 PCI/LBack in compliance
- 2020-04-01Combined UraniumMCL, Averagemeasured 37.70 PCI/L · limit 20.00 PCI/LBack in compliance
- 2020-01-01Combined UraniumMCL, Averagemeasured 38.50 PCI/L · limit 20.00 PCI/LBack in compliance
- 2019-10-01NitrateMCL, Single Samplemeasured 11.00 MG/L · limit 10.00 MG/LBack in compliance
- 2019-10-01Combined UraniumMCL, Averagemeasured 38.00 PCI/L · limit 20.00 PCI/LBack in compliance
- 2019-07-01Combined UraniumMCL, Averagemeasured 37.30 PCI/L · limit 20.00 PCI/LBack in compliance
- 2019-04-01Combined UraniumMCL, Averagemeasured 37.00 PCI/L · limit 20.00 PCI/LBack in compliance
- 2019-01-01Combined UraniumMCL, Averagemeasured 36.50 PCI/L · limit 20.00 PCI/LBack in compliance
- 2018-10-01Combined UraniumMCL, Averagemeasured 38.50 PCI/L · limit 20.00 PCI/LBack in compliance
- 2018-07-01Combined UraniumMCL, Averagemeasured 36.00 PCI/L · limit 20.00 PCI/LBack in compliance
- 2018-04-01Combined UraniumMCL, Averagemeasured 35.30 PCI/L · limit 20.00 PCI/LBack in compliance
- 2016-02-01Coliform (TCR)MCL, Monthly (TCR)Back in compliance
- 2014-01-01NitrateMCL, Single Samplemeasured 45.60 MG/L · limit 45.00 MG/LBack in compliance
- 2013-04-01NitrateMCL, Single Samplemeasured 46.40 MG/L · limit 45.00 MG/LBack in compliance
- 2013-01-01NitrateMonitoring, RegularBack in compliance
- 2012-10-01NitrateMCL, Single Samplemeasured 46.94 MG/L · limit 45.00 MG/LBack in compliance
- 2012-04-01NitrateMCL, Single Samplemeasured 47.80 MG/L · limit 45.00 MG/LBack in compliance
- 2012-01-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/RBack in compliance
- 2012-01-01NitrateMCL, Single Samplemeasured 50.00 MG/L · limit 45.00 MG/LBack in compliance
- 2011-04-01NitrateMCL, Single Samplemeasured 48.00 MG/L · limit 45.00 MG/LBack in compliance
- 2011-01-01NitrateMCL, Single Samplemeasured 58.00 MG/L · limit 45.00 MG/LBack in compliance
- 2010-10-01NitrateMCL, Single Samplemeasured 53.00 MG/L · limit 45.00 MG/LBack in compliance
- 2010-04-01NitrateMCL, Single Samplemeasured 50.00 MG/L · limit 45.00 MG/LBack in compliance
- 2010-01-01NitrateMCL, Single Samplemeasured 62.00 MG/L · limit 45.00 MG/LBack in compliance
Show the other 21 entries
- 2007-03-01Coliform (TCR)Monitoring, Routine Major (TCR)Back in compliance
- 2006-10-01NitrateMCL, Single Samplemeasured 100.00 MG/L · limit 45.00 MG/LBack in compliance
- 2006-07-01NitrateMCL, Single Samplemeasured 100.00 MG/L · limit 45.00 MG/LBack in compliance
- 2006-04-01NitrateMCL, Single Samplemeasured 100.00 MG/L · limit 45.00 MG/LBack in compliance
- 2006-01-01NitrateMCL, Single Samplemeasured 100.00 MG/L · limit 45.00 MG/LBack in compliance
- 2005-10-01NitrateMCL, Single Samplemeasured 100.00 MG/L · limit 45.00 MG/LBack in compliance
- 2005-10-01Lead and Copper RuleFollow-up Or Routine LCR Tap M/RBack in compliance
- 2005-04-01Coliform (TCR)MCL, Monthly (TCR)Back in compliance
- 2005-02-01Coliform (TCR)MCL, Monthly (TCR)Back in compliance
- 2005-01-01NitrateMCL, Single Samplemeasured 64.00 MG/L · limit 45.00 MG/LBack in compliance
- 2004-12-01NitrateMCL, Single Samplemeasured 50.00 MG/L · limit 45.00 MG/LBack in compliance
- 2004-11-01Coliform (TCR)MCL, Monthly (TCR)Back in compliance
- 2004-07-01NitrateMCL, Single Samplemeasured 94.00 MG/L · limit 45.00 MG/LBack in compliance
- 2004-01-01NitrateMonitoring, RegularBack in compliance
- 2003-10-01NitrateMonitoring, RegularBack in compliance
- 2003-07-01NitrateMCL, Single Samplemeasured 52.90 MG/L · limit 45.00 MG/LBack in compliance
- 2003-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 2002-01-01NitrateMCL, Single Samplemeasured 103.00 MG/L · limit 45.00 MG/LBack in compliance
- 2001-01-01NitrateMCL, Single Samplemeasured 56.70 MG/L · limit 45.00 MG/LBack in compliance
- 1998-01-01Coliform (TCR)Monitoring, Routine Major (TCR)Back in compliance
- 1997-08-01Coliform (TCR)MCL, Monthly (TCR)Back in compliance
System details
| Population served | 89 |
| Service connections | 27 |
| Water source | Groundwater |
| System type | Community Water System |
| Owner | Private |
| Status | Active |
| City | Chico |
| EPA ZIP on file | 95927 |
Areas served
- Tulare County
Reading this record
Del Oro River Island Serv Terr #2 is a community water system that draws from groundwater and serves about 89 people in Chico, California. Everything above comes from the EPA's Safe Drinking Water Information System (SDWIS), where states report every violation by every public water system.
Four kinds of violation. Only one is a measurement of the water: over the limit means a test came back above a legal maximum (an MCL). A treatment lapse means a required protective step was not done, such as disinfection, filtration, fixing a defect an inspector found, or filing a lead-pipe inventory. A missed or late test means a required test was skipped or never reported. That is the most common kind, and the most misread: it does not mean the water was bad, and it does not mean the water was fine. Notices and reports covers public notices and the annual Consumer Confidence Report.
Status. “Back in compliance” means the state recorded a return to compliance. “Period ended” means the violation's compliance period is over but no return to compliance was ever filed, which is common in older records. EPA's federal copy lags state records by months, so call the utility for anything current.