City of Yates Center
A missed test is not evidence of bad water. It also is not evidence of good water: for that period nobody checked.
On record since 1999: 31 violations. 8 over the limit · 8 treatment lapses · 9 missed or late tests · 6 notices or reports. Most recent began 2025-07-02.
For this year's test results, ask the utility for its annual Consumer Confidence Report. Every community system must publish one.
More violations on record than 91% of active water systems in Kansas. Small systems with no staff chemist often rack up missed-test violations; big utilities rarely do.
The record, year by year
Across Kansas, 52% of violations are missed or late tests and 13% are water over a limit.
How far over the limit
Lead & copper at the tap
Utilities sample taps in homes most likely to have lead pipes, and report the 90th-percentile result: 9 in 10 homes sampled came in at or below this number. Above the red line (the action level) the utility must act. The action level is not a safe level; EPA's health goal for lead is zero. EPA's file does not date these results, so they are shown highest first.
Lead, 90th percentile 4 results on file · action level 15 ppb
Open now (1)
- 2025-07-02Lead service line inventoryRPTOpen
Every violation on record
- 2025-07-02Lead service line inventoryRPTOpen
- 2025-07-01ChloriteMonitoring and Reporting (DBP)Period ended · no return to compliance on file
- 2025-07-01Carbon, TotalTreatment Technique Precursor Removalmeasured 0.4900 RATIOPeriod ended · no return to compliance on file
- 2025-04-01Carbon, TotalTreatment Technique Precursor Removalmeasured 0.5300 RATIOPeriod ended · no return to compliance on file
- 2025-03-01Carbon, TotalMonitoring and Reporting (DBP)Period ended · no return to compliance on file
- 2025-01-01Carbon, TotalTreatment Technique Precursor Removalmeasured 0.5600 RATIOPeriod ended · no return to compliance on file
- 2025-01-01Carbon, TotalMonitoring and Reporting (DBP)Period ended · no return to compliance on file
- 2025-01-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0780 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2024-10-01Carbon, TotalTreatment Technique Precursor Removalmeasured 0.7400 RATIO · limit 1.00 RATIOPeriod ended · no return to compliance on file
- 2024-10-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0980 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2024-09-01Surface water treatment (SWTR)Monitoring of Treatment (SWTR-Filter)Back in compliance
- 2024-08-01ChloriteMonitoring and Reporting (DBP)Back in compliance
- 2024-07-01Carbon, TotalTreatment Technique Precursor Removalmeasured 0.7400 RATIO · limit 1.00 RATIOPeriod ended · no return to compliance on file
- 2024-07-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0990 MG/L · limit 0.0600 MG/LBack in compliance
- 2024-04-01ChloriteMCL, Averagemeasured 1.30 MG/L · limit 1.00 MG/LBack in compliance
- 2024-04-01Carbon, TotalTreatment Technique Precursor Removalmeasured 0.8200 RATIOPeriod ended · no return to compliance on file
- 2024-04-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0990 MG/L · limit 0.0600 MG/LBack in compliance
- 2024-01-01Carbon, TotalTreatment Technique Precursor RemovalBack in compliance
- 2024-01-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0770 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2023-10-01Total Haloacetic Acids (HAA5)Failure Submit IDSE/Subpart V Plan RptBack in compliance
- 2023-10-01Carbon, TotalTreatment Technique Precursor Removalmeasured 0.9200 RATIOBack in compliance
- 2023-10-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0620 MG/L · limit 0.0600 MG/LPeriod ended · no return to compliance on file
- 2023-09-01ChloriteMCL, Averagemeasured 1.30 MG/L · limit 1.00 MG/LBack in compliance
- 2020-11-01Surface water treatment (SWTR)Monitoring of Treatment (SWTR-Filter)Back in compliance
- 2020-11-01Surface water filtration (IESWTR)Monitoring, Turbidity (Enhanced SWTR)Back in compliance
Show the other 6 entries
- 2019-12-30Lead and Copper RuleLead Consumer NoticeBack in compliance
- 2010-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 2004-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 2003-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 2000-07-01Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
- 1999-10-19Consumer Confidence RuleCCR Complete Failure to ReportBack in compliance
System details
| Population served | 1,335 |
| Service connections | 833 |
| Water source | Surface Water |
| System type | Community Water System |
| Owner | Local Government |
| Status | Active |
| City | Yates Center |
| EPA ZIP on file | 66783 |
Areas served
- Yates Center, Woodson County
Reading this record
City of Yates Center is a community water system that draws from surface water and serves about 1,335 people in Yates Center, Kansas. Everything above comes from the EPA's Safe Drinking Water Information System (SDWIS), where states report every violation by every public water system.
Four kinds of violation. Only one is a measurement of the water: over the limit means a test came back above a legal maximum (an MCL). A treatment lapse means a required protective step was not done, such as disinfection, filtration, fixing a defect an inspector found, or filing a lead-pipe inventory. A missed or late test means a required test was skipped or never reported. That is the most common kind, and the most misread: it does not mean the water was bad, and it does not mean the water was fine. Notices and reports covers public notices and the annual Consumer Confidence Report.
Status. “Back in compliance” means the state recorded a return to compliance. “Period ended” means the violation's compliance period is over but no return to compliance was ever filed, which is common in older records. EPA's federal copy lags state records by months, so call the utility for anything current.