Community Water System · PWSID CA5700555

Bonfire Village Hotel

Serves 44 peopleGroundwaterOwner: PrivateSacramento, California
Nothing open right now.

On record since 2010: 27 violations. 15 over the limit · 12 missed or late tests. Most recent began 2025-04-01.

For this year's test results, ask the utility for its annual Consumer Confidence Report. Every community system must publish one.

15Over the limit
0Treatment lapse
12Missed or late test
0Notice or report

More violations on record than 95% of active water systems in California. Small systems with no staff chemist often rack up missed-test violations; big utilities rarely do.

The record, year by year

20052010 · Missed or late test: 120102011 · Missed or late test: 12012 · Missed or late test: 12013 · Missed or late test: 22013 · Missed or late test: 22014 · Missed or late test: 12015 · Missed or late test: 120152016 · Missed or late test: 12017 · Over the limit: 12017 · Missed or late test: 22017 · Missed or late test: 22019 · Missed or late test: 12020 · Missed or late test: 120202021 · Over the limit: 22021 · Over the limit: 22022 · Over the limit: 42022 · Over the limit: 42022 · Over the limit: 42022 · Over the limit: 42023 · Over the limit: 32023 · Over the limit: 32023 · Over the limit: 32024 · Over the limit: 32024 · Over the limit: 32024 · Over the limit: 32025 · Over the limit: 22025 · Over the limit: 22025
One square = one violation, by the year it began. Empty columns are years with nothing on EPA's record.
56% over the limit · 1544% missed or late test · 12

Across California, 52% of violations are missed or late tests and 29% are water over a limit.

How far over the limit

at the limit2×5×10×100×+Nitrate2025-04-01 · Nitrate: measured 21.00 MG/L vs limit 10.00 MG/L (2.1×)2025-01-01 · Nitrate: measured 17.00 MG/L vs limit 10.00 MG/L (1.7×)2024-10-01 · Nitrate: measured 20.00 MG/L vs limit 10.00 MG/L (2.0×)2024-07-01 · Nitrate: measured 20.00 MG/L vs limit 10.00 MG/L (2.0×)2024-01-01 · Nitrate: measured 21.00 MG/L vs limit 10.00 MG/L (2.1×)2023-10-01 · Nitrate: measured 19.00 MG/L vs limit 10.00 MG/L (1.9×)2023-04-01 · Nitrate: measured 11.00 MG/L vs limit 10.00 MG/L (1.1×)2022-10-01 · Nitrate: measured 11.00 MG/L vs limit 10.00 MG/L (1.1×)2022-07-01 · Nitrate: measured 13.00 MG/L vs limit 10.00 MG/L (1.3×)2022-04-01 · Nitrate: measured 15.00 MG/L vs limit 10.00 MG/L (1.5×)2022-01-01 · Nitrate: measured 14.00 MG/L vs limit 10.00 MG/L (1.4×)2021-07-01 · Nitrate: measured 13.90 MG/L vs limit 10.00 MG/L (1.4×)2021-04-01 · Nitrate: measured 13.00 MG/L vs limit 10.00 MG/L (1.3×)2017-06-01 · Nitrate: measured 11.88 MG/L vs limit 10.00 MG/L (1.2×)
Each dot is one over-the-limit violation: the measured value divided by the limit it broke, on a log scale. Most legal limits for chemicals are running averages set for a lifetime of drinking, so “just over” and “ten times over” are very different news. Hover a dot for the numbers.

Lead & copper at the tap

Utilities sample taps in homes most likely to have lead pipes, and report the 90th-percentile result: 9 in 10 homes sampled came in at or below this number. Above the red line (the action level) the utility must act. The action level is not a safe level; EPA's health goal for lead is zero. EPA's file does not date these results, so they are shown highest first.

Lead, 90th percentile 4 results on file · action level 15 ppb

0 ppb
0 ppb
0 ppb
0 ppb

Every violation on record

  1. 2025-04-01NitrateMCL, Averagemeasured 21.00 MG/L · limit 10.00 MG/LPeriod ended · no return to compliance on file
  2. 2025-01-01NitrateMCL, Averagemeasured 17.00 MG/L · limit 10.00 MG/LPeriod ended · no return to compliance on file
  3. 2024-10-01NitrateMCL, Averagemeasured 20.00 MG/L · limit 10.00 MG/LPeriod ended · no return to compliance on file
  4. 2024-07-01NitrateMCL, Averagemeasured 20.00 MG/L · limit 10.00 MG/LPeriod ended · no return to compliance on file
  5. 2024-01-01NitrateMCL, Single Samplemeasured 21.00 MG/L · limit 10.00 MG/LPeriod ended · no return to compliance on file
  6. 2023-10-01NitrateMCL, Single Samplemeasured 19.00 MG/L · limit 10.00 MG/LPeriod ended · no return to compliance on file
  7. 2023-07-01NitrateMCL, Averagemeasured 18.00 MG/LPeriod ended · no return to compliance on file
  8. 2023-04-01NitrateMCL, Single Samplemeasured 11.00 MG/L · limit 10.00 MG/LPeriod ended · no return to compliance on file
  9. 2022-10-01NitrateMCL, Averagemeasured 11.00 MG/L · limit 10.00 MG/LPeriod ended · no return to compliance on file
  10. 2022-07-01NitrateMCL, Averagemeasured 13.00 MG/L · limit 10.00 MG/LPeriod ended · no return to compliance on file
  11. 2022-04-01NitrateMCL, Averagemeasured 15.00 MG/L · limit 10.00 MG/LPeriod ended · no return to compliance on file
  12. 2022-01-01NitrateMCL, Averagemeasured 14.00 MG/L · limit 10.00 MG/LPeriod ended · no return to compliance on file
  13. 2021-07-01NitrateMCL, Averagemeasured 13.90 MG/L · limit 10.00 MG/LPeriod ended · no return to compliance on file
  14. 2021-04-01NitrateMCL, Averagemeasured 13.00 MG/L · limit 10.00 MG/LPeriod ended · no return to compliance on file
  15. 2020-10-01Revised Total Coliform RuleMONBack in compliance
  16. 2019-06-01Revised Total Coliform RuleMONBack in compliance
  17. 2017-06-01NitrateMCL, Averagemeasured 11.88 MG/L · limit 10.00 MG/LBack in compliance
  18. 2017-01-01NitriteMonitoring, RegularBack in compliance
  19. 2017-01-01NitrateMonitoring, RegularBack in compliance
  20. 2016-10-01NitrateMonitoring, RegularBack in compliance
  21. 2015-01-01NitrateMonitoring, RegularBack in compliance
  22. 2014-01-01NitrateMonitoring, RegularBack in compliance
  23. 2013-01-01NitriteMonitoring, RegularBack in compliance
  24. 2013-01-01NitrateMonitoring, RegularBack in compliance
  25. 2012-01-01NitrateMonitoring, RegularBack in compliance
Show the other 2 entries
  1. 2011-01-01NitrateMonitoring, RegularBack in compliance
  2. 2010-01-01NitriteMonitoring, RegularBack in compliance

System details

Population served44
Service connections3
Water sourceGroundwater
System typeCommunity Water System
OwnerPrivate
StatusActive
CitySacramento
EPA ZIP on file95835

Areas served

  • Yolo County

Reading this record

Bonfire Village Hotel is a community water system that draws from groundwater and serves about 44 people in Sacramento, California. Everything above comes from the EPA's Safe Drinking Water Information System (SDWIS), where states report every violation by every public water system.

Four kinds of violation. Only one is a measurement of the water: over the limit means a test came back above a legal maximum (an MCL). A treatment lapse means a required protective step was not done, such as disinfection, filtration, fixing a defect an inspector found, or filing a lead-pipe inventory. A missed or late test means a required test was skipped or never reported. That is the most common kind, and the most misread: it does not mean the water was bad, and it does not mean the water was fine. Notices and reports covers public notices and the annual Consumer Confidence Report.

Status. “Back in compliance” means the state recorded a return to compliance. “Period ended” means the violation's compliance period is over but no return to compliance was ever filed, which is common in older records. EPA's federal copy lags state records by months, so call the utility for anything current.