Community Water System · PWSID ID1110001

Bee Line Water Assn Inc

Serves 533 peopleSurface WaterOwner: PrivateBonners Ferry, Idaho
Nothing open right now.

On record since 1994: 13 violations. 5 over the limit · 1 treatment lapse · 7 missed or late tests. Most recent began 2025-07-01.

For this year's test results, ask the utility for its annual Consumer Confidence Report. Every community system must publish one.

5Over the limit
1Treatment lapse
7Missed or late test
0Notice or report

More violations on record than 79% of active water systems in Idaho. Small systems with no staff chemist often rack up missed-test violations; big utilities rarely do.

The record, year by year

1994 · Missed or late test: 1199520002005201020152016 · Over the limit: 42016 · Over the limit: 42016 · Over the limit: 42016 · Over the limit: 42017 · Over the limit: 12017 · Missed or late test: 12019 · Treatment lapse: 12020 · Missed or late test: 42020 · Missed or late test: 42020 · Missed or late test: 42020 · Missed or late test: 420202025 · Missed or late test: 12025
One square = one violation, by the year it began. Empty columns are years with nothing on EPA's record.
38% over the limit · 58% treatment lapse · 154% missed or late test · 7

Across Idaho, 80% of violations are missed or late tests and 5% are water over a limit.

How far over the limit

at the limit2×5×10×100×+Total Haloacetic Acids (HAA5)2017-04-01 · Total Haloacetic Acids (HAA5): measured 0.0620 MG/L vs limit 0.0600 MG/L (1.0×)2016-07-01 · Total Haloacetic Acids (HAA5): measured 0.0740 MG/L vs limit 0.0600 MG/L (1.2×)2016-04-01 · Total Haloacetic Acids (HAA5): measured 0.0720 MG/L vs limit 0.0600 MG/L (1.2×)2016-01-01 · Total Haloacetic Acids (HAA5): measured 0.0790 MG/L vs limit 0.0600 MG/L (1.3×)2016-01-01 · Total Haloacetic Acids (HAA5): measured 0.0790 MG/L vs limit 0.0600 MG/L (1.3×)
Each dot is one over-the-limit violation: the measured value divided by the limit it broke, on a log scale. Most legal limits for chemicals are running averages set for a lifetime of drinking, so “just over” and “ten times over” are very different news. Hover a dot for the numbers.

Lead & copper at the tap

Utilities sample taps in homes most likely to have lead pipes, and report the 90th-percentile result: 9 in 10 homes sampled came in at or below this number. Above the red line (the action level) the utility must act. The action level is not a safe level; EPA's health goal for lead is zero. EPA's file does not date these results, so they are shown highest first.

Lead, 90th percentile 7 results on file · action level 15 ppb

7 ppb
7 ppb
5.4 ppb
4 ppb
4 ppb
2 ppb
1 ppb

Every violation on record

  1. 2025-07-01Carbon, TotalMonitoring and Reporting (DBP)Period ended · no return to compliance on file
  2. 2020-04-01Total Haloacetic Acids (HAA5)Monitoring and Reporting (DBP)Back in compliance
  3. 2020-02-01Surface water treatment (SWTR)Monitoring of Treatment (SWTR-Filter)Period ended · no return to compliance on file
  4. 2020-02-01Revised Total Coliform RuleMONBack in compliance
  5. 2020-01-01ChlorineMonitoring and Reporting (DBP)Back in compliance
  6. 2019-12-01Surface water treatment (SWTR)Treatment Technique (SWTR and GWR)Back in compliance
  7. 2017-04-01Trihalomethanes (TTHM)Monitoring and Reporting (DBP)Back in compliance
  8. 2017-04-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0620 MG/L · limit 0.0600 MG/LBack in compliance
  9. 2016-07-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0740 MG/L · limit 0.0600 MG/LBack in compliance
  10. 2016-04-01Total Haloacetic Acids (HAA5)MCL, Averagemeasured 0.0720 MG/L · limit 0.0600 MG/LBack in compliance
  11. 2016-01-01Total Haloacetic Acids (HAA5) ×2MCL, Averagemeasured 0.0790 MG/L · limit 0.0600 MG/LBack in compliance
  12. 1994-01-02Lead and Copper RuleInitial Tap Sampling for Pb and CuBack in compliance

System details

Population served533
Service connections213
Water sourceSurface Water
System typeCommunity Water System
OwnerPrivate
StatusActive
CityBonners Ferry
EPA ZIP on file83805

Areas served

  • Boundary County

Reading this record

Bee Line Water Assn Inc is a community water system that draws from surface water and serves about 533 people in Bonners Ferry, Idaho. Everything above comes from the EPA's Safe Drinking Water Information System (SDWIS), where states report every violation by every public water system.

Four kinds of violation. Only one is a measurement of the water: over the limit means a test came back above a legal maximum (an MCL). A treatment lapse means a required protective step was not done, such as disinfection, filtration, fixing a defect an inspector found, or filing a lead-pipe inventory. A missed or late test means a required test was skipped or never reported. That is the most common kind, and the most misread: it does not mean the water was bad, and it does not mean the water was fine. Notices and reports covers public notices and the annual Consumer Confidence Report.

Status. “Back in compliance” means the state recorded a return to compliance. “Period ended” means the violation's compliance period is over but no return to compliance was ever filed, which is common in older records. EPA's federal copy lags state records by months, so call the utility for anything current.